STANDARD FEATURES
- 6 Pulse (for 3 Phase)
- Input Transformer for Galvanic Isolation
- Front Panel with LCD Screen (2 Lines), LED Indication and MIMIC diagram
- Digital Metering on LCD including, Input Voltage and Current (for 1 Phase), Battery Voltage and Current, Load Voltage, Charger Output Current
- Redundant Supply for LCD
- Separate Battery Charge Current and Output Current Adjustment via Current Transformer
- Output LC Filter
- Transient Surge Protection (via Varistor)
- Input MCB with Auxiliary Contacts
- Load and Battery MCB (up to 60A) with Auxiliary Contacts
- Load and Battery NH Fuse (higher than 60A) with Auxiliary Contacts
- Forced Ventilation with Smart Fan
- Event History up to 250 Events
- 8 Free Contacts
- Automatic Online Battery Performance Test
- Automatic and Manual Boost Function
OPTIONAL FEATURES
- 12 Pulse (3 Phase), THDi ≤ 10%, (PF) ≥ 0.85 Inductive
- 12 Pulse (3 Phase) with Active Harmonic Elimination, THDi ≤ 5%, (PF) ≥ 0.95 Inductive
- LCD Screen (4 Lines)
- Digital Metering on LCD Input Current (for 3 Phase)
- Analogue AC or DC Voltmeter and Ammeter
- Dropper Diodes
- DC/DC Converter (Can be used as a voltage stabilizer instead of dropper diodes)
- LVD (Battery deep discharge protection contactor)
- SCR Fuse (Semiconductor Fast Fuse)
- Transient Surge Protection (via Surge Arrester)
- Input, Load and Battery MCCB
- Front Access Industrial Enclosure
- Battery and Battery Charger Inside Same Enclosure
- Natural Ventilation
- Custom IP Protection
- Custom Paint
- Enclosure Heater and Lighting
- Internal or External Distribution
- Forced/Active Load Sharing in Parallel Configuration
- Battery Temperature Compensation
- 8 Free Contacts (Configurable via Communication interface)
- Communication (PC Remote, Modbus, SNMP, Profibus, DNP 3.0 via RS 232, RS 485 or Ethernet TCP/IP ports)
SPECIFICATION
GENERAL | |
---|---|
Model | RDA / RDAT series |
Topology | Full Bridge Phase Angle Controlled Thyristor Module Rectifier |
Control | Microprocessor Controlled System |
INPUT | |
---|---|
Input Isolation Transformer | Galvanically isolated / Primary & Secondary Earth Screened |
Nominal Voltage and Tolerance | 110/127/190/200/220/230/240/380/400/415/480 VAC ±15% (1 Phase or 3 Phase) |
Nominal Frequency | 50 Hz / 60Hz ±5% |
Cosφ | ≥ 0.8 Inductive (6 Pulse) ≥ 0.85 Inductive (12 Pulse) ≥ 0.95 Inductive (12 Pulse with active harmonic elimination) |
Total harmonic Distortion (THDi) | ≤ 30% (6 Pulse), ≤ 10% (12 Pulse), ≤ 5% (12 Pulse with active harmonic elimination) |
Input Protection | Input: Thermic-Magnetic Over Current Protection, Over Voltage Protection, Phase Sequence Free Operation (3 Phase), Soft Start, MCB |
OUTPUT | |
---|---|
Battery Charging Principle | Constant Current/ Constant Voltage |
Rated Power | Depends on DC voltage and Current |
Nominal Output Voltage | 12 / 24 / 48 / 110 / 125 / 220 / 264 / 360 / 450 / 900VDC |
Output Current Adjustment | 0-100% of Nominal Output Current |
Static Tolerance | ±1% (Lower values available upon request) |
Output Voltage Ripple RMS | ≤ 1% RMS AC of Output Voltage |
Boost voltage (V/C) | 2,4 lead acid battery 1,60 NiCd Battery (Depends on battery manufacturer recommendation) |
Float voltage (V/C) | 2,23 lead acid battery 1,40 NiCd battery (Depends on battery manufacturer recommendation) |
Dynamic Response Time and Voltage Variation | <50msec, <+/-5% (for 10% – 100%, 100% – 10% step load change) |
CONTROL ELEMENTS | |
---|---|
Battery Test | Automatic or manual selectable. Please refer to user manual for details |
Boost Timer | 0 – 99,9 hours adjustable by 1 minute accuracy |
Current Limitation | Total output current and battery current can be adjusted separately |
ALARM CONTACTS | |
---|---|
Open or closed free alarm contacts | “Low Battery, Mains Input Normal / Failure, Charger Failure, Overtemperature, Charger Overvoltage, Load MCB ON/ OFF, Battery MCB ON / OFF, Earth Fault” |
DISPLAY PANEL & MEASUREMENT | |
---|---|
Measurements | LCD Display for Line Voltage / Frequency / Current (Standard in 1 Phase, Optional for 3 Phase), Battery Output Voltage / Current, Load Output Voltage, Charger Total Output Current |
Indicators | Float Mode, Boost Mode, Current Mode, Equalize Mode, Battery Ending, Low Battery, Battery Test Failure, Line Failure, Fan Failure, Over Voltage, Under Voltage, Over Temperature, Rectifier Failure, SCR Fuse Failure, Mains Available, Load MCB, Battery MCB |
Adjustable Parameters | Float Charge Voltage, Boost Charge Voltage, Equalize Charge Voltage, Battery Charge Current, Rectifier Total Output Current, Low Battery Voltage Alarm, Earth Fault Leakage Current Alarm (only available in 4 line LCD), Battery Ending Voltage Alarm, Online Battery Test Parameters, Auto Boost Charge Parameters, Password |
Event History | Last 250 events recorded and displayed on front panel and on PC via remote communication |
Sound Alarm | On Warning Messages 2 Short ‘beep’ per 2 seconds |
COMMUNICATION AND PARALLELING | |
---|---|
Communication (OPTIONAL) | RS 485 / RS 232 / Ethernet Ports, Remote PC Control, Modbus, Profibus, SNMP, DNP 3.0 Protocols and TCP/IP options |
Paralleling (OPTIONAL) | Redundant Operation of Dual Chargers with Forced (Active) Load Sharing Option |
LVD | |
---|---|
LVD (OPTIONAL) | Protection of Battery from Deep Discharge via Contactor. Available on request |
DROPPER DIODES | |
---|---|
Dropper Diodes (OPTIONAL) | Dropper Diodes for Float and Boost Voltage Regulations. Available on request |
SAFETY & ENVIRONMENT | |
---|---|
Circuit Breakers | Input: Miniatur circuit breakers; Output: Miniatur circuit breakers / NH Fuse; Battery: Miniatur circuit breakers / NH Fuse |
Over Voltage Protection | IEEE 587 4500 A, 110 Joules (standard) / 40kA Surge Arrestor (OPTIONAL) |
Electrical Interference Reduction | FCC Part 15 Class B |
Electrical Standards | EN 50091-1 (Security) / EN 50091-2 (EMC) |
Protection Level / Color | IP 20 / RAL 7035 (Standard), (Higher IP rating and different colors are available, please consult) |
Isolation Voltage | 2000VAC input/chassis and output/chassis |
MTBF | 100,000 hrs. (w/out battery group) |
Enclosure Material | Mild Steel, Zinc-phosphate coated; 100 µm electrostatic paint; 1.5 mm thickness |
Cooling | Forced fans / Natural (optional) |
Cable Entry | Bottom / Top (optional) |
Distribution | OPTIONAL |
Heater & Lightning | OPTIONAL |
Operating Temperature | -10 / +40 °C. Higher operating temperatures are available, please consult |
Relative humidity | 5 – 90 % |
Operating Altitude | Max. 1000 Mt. (Higher altitudes requires de-rating, please consult ) |
Noise Level | Max. 65 db |